Zone controls line

Taco ZVC404 vs. SR Switching Relays for Hydronic Zoning

Choose a Taco ZVC404 or SR switching relay by identifying what controls flow in each zone. Check valve wire count, pump voltage, and hot water priority.

Illustrated title card for the guide: Taco ZVC404 vs. SR Switching Relays for Hydronic Zoning

Choose a Taco ZVC zone valve control when motorized valves open the heating zones and a shared circulator moves water through them. Consider the ZVC404 if the model documentation confirms it supports the number of zones you need. Choose a Taco SR switching relay when each zone has a dedicated circulator that starts on a call for heat. Taco zone valve controls · Taco switching relays · Valve zoning layout · Circulator zoning layout

Match the panel to the piping

Find what controls flow on each space-heating branch. A system with motorized zone valves can also have a separate boiler circulator, so check what serves each branch before you count pumps. Caleffi valve zoning layouts, figures 3-1a and 3-1b

What you find on the heating branchesWhat happens on a call for heatPanel family
A motorized valve on each branch and one circulator serving those branchesThe calling zone’s valve opens. The shared circulator supplies the active branches.ZVC zone valve control
A dedicated circulator on each branchThe calling zone’s circulator starts.SR switching relay

For example, four thermostats that each open a valve on piping served by a shared circulator point to a ZVC. Four thermostats that each start their own zone circulator point to an SR. Caleffi valve zoning · Caleffi circulator zoning

Compare the exact model numbers

For Taco’s Next Generation line, look up ZVC404-5 under Zone Valve Controls and SR504-5 under Switching Relays. Taco lists support for 2-, 3- and 4-wire zone valves and up to three pumps through pump end switches on the ZVC line. The SR line lists a switchable primary circulator output. Both lines list switchable priority. Taco Next Generation ZVC · Taco Next Generation SR

Check these items before ordering

Evidence and limits. This comparison is based on Taco’s ZVC404 and SR product documentation, including the Next Generation -5 series, and Caleffi’s Zoning with Motorized Valves (i36) and Zoning with Circulators (i36). The checks were not performed on installed equipment.

Sources

The published documents this guide is built from.

  1. Taco Zone Valve Controls
  2. Taco Enhanced Switching Relays
  3. Taco Next Generation Zone Valve Controls
  4. Taco Next Generation Switching Relays
  5. Caleffi Zoning with Motorized Valves (i36)
  6. Caleffi Zoning with Circulators (i36)