Loop flow estimate
Enter one zone's heat load and its design temperature drop. The estimate gives the water flow the zone needs, in total and split across its loops. It runs in your browser and nothing you type is sent anywhere.
Estimate Flow for this zone
Enter a heat load and a temperature drop to see the estimate.
How the estimate works
Water carries heat out to the rooms and comes back cooler. The heat it hands over equals the flow times the temperature drop times what each unit of water can carry, so the flow is the heat load divided by the other two.
US: GPM = BTU/h ÷ (500 × ΔT °F)
Metric: L/min = W × 60 ÷ (4180 × ΔT K)
Per loop = total flow ÷ number of loops
Return temperature = supply temperature − temperature drop
Assumptions
- The estimate assumes steady heat transfer and fixed water properties. Real water properties vary with temperature.
- The fluid is plain water. Glycol mixtures need their own fluid properties and usually more flow than this shows.
- The 500 factor is rounded from 8.33 lb of water per US gallon × 60 minutes per hour × 1 BTU per lb per °F (which is 499.8), using approximate properties for water near 60 °F.
- The metric line uses 4180 J per kg per kelvin for the specific heat of water and 1000 kg per cubic metre (1 kg per litre) for its density, the approximations the ASHRAE Handbook gives for metric units.
- A temperature drop in °C is the same size as one in kelvin.
- The per-loop figure assumes every loop on the zone takes an equal share. Real loops differ in length, and the manifold's balancing settings set each loop's share. A blank loop count means one loop.
- The "same flow" figure converts with 1 US gallon = 3.785411784 litres. It is the same flow in other units, not a second calculation.
- It does not size pumps, pipes or pressure drop, and it is not a design. Use the manifold or zone panel maker's design guide and a qualified installer.
Calculator limits
These are limits of this calculator, not properties of the equations. It accepts one zone's heat load from 100 to 1,000,000 BTU/h (30 to 300,000 W), a temperature drop from 1 to 100 °F (0.5 to 55 K), a whole number of loops from 1 to 50 (blank means one), and a supply temperature above freezing and up to boiling for plain water at ordinary atmospheric pressure (above 32 up to 212 °F, or above 0 up to 100 °C), with the return also above freezing. Numbers use a dot for decimals, for example 5.5. Commas that group thousands, as in 12,000, are accepted.
The example button fills round made-up numbers. Use the figures from your own heat-loss calculation. Changing units clears the heat load, drop and supply fields, because the same digits mean something different in the other units.
Sources
- 5. Physical Operating Conditions in Hydronic Systems, Formula 5-3 (Caleffi S.p.a.): the US rule, flow in GPM from heat in BTU/h with the 500 factor.
- Chapter 13: Hydronic Heating and Cooling, equations 7 to 9 (ASHRAE Handbook): the heat balance and its metric approximation of 4.18 kJ/(kg·K) and 1000 kg/m³.
- Table 4-20M: Energy Intensity of Passenger Modes (U.S. Department of Transportation, Bureau of Transportation Statistics): prints the US gallon as 3.785411784 litres.
- NIST Guide to the SI, Appendix B.8: Factors for Units Listed Alphabetically (National Institute of Standards and Technology): the gallon factor, correctly rounded to 3.785412 litres in the table.
- SI Units: Temperature (National Institute of Standards and Technology): degree Celsius and kelvin intervals are equal, and the freezing and boiling reference points used as calculator limits.